Features & Protections
Phase failure / loss from supply and motor side.
Phase reversal / wrong phase sequence from supply side.
Phase to phase current unbalance 50 % of set current.
Electronic overload.
Remote sensing dry run / No load current.
Extreme high current (EHC) or short circuit as per pump current.
Technology
Microcontroller based digital product with high reliability and long life.


World class MCU and software which is highly fault tolerant to noise and
Electro magnetic interferences and noise from motor, starter etc.
SMPS based power supply works from 200 to 500 volts.

Produced in ISO 9001: 2000 certified company.
Control Settings


Star delta starter with khyatee make heavy duty 40 amps, 4 pole AC coil Contactors Or as required i.e. Siemens, L&T etc for long life.

Pump current setting is easy, accurate, auto setting type, with digital display.
Pump current setting range is 2-14 for 5-10 hp or.

Pump current setting range 8-20 amps for 10-15 hp or.
Pump current setting range 18-34 amps for 20-30 hp.

Overload is site selectable from 20 to 50 % of set current.
Dry run setting from 75 to 95 % in increment of 1 % amps.

Dry run bypasses facility with digital display.
Site selectable Auto / Manual operation switch.
Monitoring
Calibrated Digital Voltmeter with 200 to 500 volt ± 2 volt. Accuracy.

Calibrated Digital Ammeter 0.5 to 28 amps ± 0.2 amps Accuracy.
Digital display for fault ampere at tripping.
In built memory to show last setting value.
On site AUTO FAULT DETECT (AFT) for AC voltage, LEDS, Display, Relay, etc.
Timers
Site selectable star to delta timer from 10 to 99 seconds.

Digital display for countdown timer.
On delay timer for one minute for auto start for power failure and SPP faults.

Time delay to filter power on spikes and surges.
Additional Features
Widest working voltage range from 200 to 500 volts.

Three pole MCB of required amps for short circuit and main switch.
Unit has heavy duty ON – OFF, Setting and Auto / Manual switches.
Color coded ISI grade Teflon wiring with lugs for longer life.
Modular design very easy to install and site servicing.
Heavy duty terminal for input / output connections.


Eliminates the need for separate star delta starter, auto switch, voltmeter and ammeter.
Indications & Displays
Auto scrolling display for updated pump current and line voltage.
Countdown display for star delta timer.
Ultra bright indicators for all faults.
Early fault warnings by blinking LED.
Value of tripping current / voltage.
Setting.
SPP/ RP / VUB.
Overload.
Dry run.
Voltage.
R phase.
Y phase.
B phase.
Enclosures & Mountings
Compact, vermin proof, rust proof, mild steel powder coated panel box.
Size :
Weight :
Mounting : wall.
Options
Model KDM 2-20 SDCS for 5 to 12.5 Hp.
Model KDM 2-30 SDCS for 7.5 to 20 Hp.
Model KDM 2-40 amps for 20-30 hp.

Pump control panels and starters
With start and run capacitors
KDP 22 DS
KDP 99 WLC
KSR 22
KSD 22
With only running capacitors
KTC 33 WLC (Digital)
KSP 22
KTC 22
TC 22
Single phase starter
SS 22
DOL SERIES
KDM 216 CS
KDM 2-30 panel
KTP 99 DRA
KSI 33 MCB
KSI 33 MINI
START DELTA SERIES
Star delta panels
         
Home About Us Products Mobile Starters & Panels Downloads
About Us Management Pump control panels and starters Mobile starter with external phone Khyatee Mobile Starter English
Products Vision & Mission Mobile starters and panels KMS 33 Khyatee Mobile Starter Marathi
Products Gallery Value Statement GSM- wireless monitor and control KMS Mini M3 Khyatee Mobile Starter M3 Unit
Downloads Quality Policy Medical Products M3 Unit Mobile Starter Manual
Contact Us Milestones Hydro pneumatic automation Mobile Starter Chart  
Facebook Accreditations Liquid level automation    
You Tube Why Khyatee Domestic home care series Mobile Starter with inbuilt GSM SIM  
    Energy management M4 Display SIM  
    Water / RO plant automation M5 GSM LCD  
    Phase failure relays    
    Timers    
2012 All Rights Reserved.   Powerd by :: Cosmic ::